External CFD simulation of a data center of several tens of megawatts: the video compares the path of the wind and of the hot air discharges for a south-west wind, then a north-east wind.
Updated on 25 November 2026
In under two minutes, we see that the same installation behaves differently depending on the wind: the plumes move away or bend back down onto the roof. This is what determines the risk of recirculation for the dry coolers.
Click a passage to play it in the player.
This video comes from the external and internal CFD study of a hyperscale data center of several tens of megawatts, carried out by EOLIOS. It presents the external part: the path of the hot air discharged by the rooftop equipment.
Two wind directions are compared, south-west then north-east. For each, we first see the streamlines of the wind over the site, then a temperature isosurface enveloping the hot air plumes above the building.
Outside a data center, the impact of thermal plumes is hard to predict: it depends on wind speed and direction, air temperature and the site's surroundings.
A surface that connects all points at the same temperature. Around a data center, it outlines the hot air discharged on the roof.
EOLIOS simulated the inside and outside of the building to control hot spots, thermal recirculation and the available cooling capacity, including in failure scenarios.
View the full study: external and internal CFD of a hyperscale data centerThe video shows the external part for two wind directions. The full study also presents the results in the data halls, the recirculation identified and the optimisations proposed.
View the study results: external and internal CFD of a hyperscale data centerThe video, the hot air plumes and the link with the data center study.
An external CFD simulation of a hyperscale data center: the wind's streamlines, then the hot air plumes on the roof, for a south-west wind and a north-east wind.
On the streamlines, they represent wind speed. On the isosurfaces, they show the temperature of the discharged hot air.
Depending on where the wind comes from, the plumes go one way or the other and can bend down onto different equipment.
It is the re-intake, by a dry cooler, of part of the hot air discharged nearby. It reduces cooling capacity.
The internal and external results and the proposed optimisations are presented in the full hyperscale data center study.
Explore our expertise, projects and technical papers to go further than the FAQ.
CFD expertise, delivered projects and technical dossiers: the whole Data Center field in one place.
The simplest thing is to talk it through together. Our engineers reply with an initial technical read.