Home/Resources/Videos/Plumes of a data center in Meudon
inShare on LinkedIn
Video · Data Center

Rooftop plumes at a data center in Meudon.

External CFD simulation of a data center in Meudon: the hot air plumes from the dry coolers and generator sets, then their path over the wooded site.

Updated on 25 November 2026

Video
CFD simulation
Duration
1 min 32
Year
2024
Location
Meudon, France
Typology
Data Center
Key takeaway

In a minute and a half, we see how the discharges from a data center rise, mix and disperse over a site surrounded by woods and buildings.

Key moments in the video

Click a passage to play it in the player.

What the video shows: hot air discharged on the roof

This video comes from EOLIOS's external CFD study of the PA22 data center in Meudon. The site's dry coolers and generator sets discharge hot air on the roof.

A temperature isosurface envelops the hot air above the equipment, then streamlines show the generator set discharges. The video ends with the plume carried over the wooded site.

Where does this video come from? Cooling a data center in Meudon

The dry coolers are installed on the roof of the technical rooms that house the generator sets. It had to be confirmed that generator exhaust would not contaminate the air they draw in.

Definition · Dry cooler

Equipment that releases heat from a water circuit into the outside air using fans. It discharges hot air, and its performance depends on the temperature of the air it draws in.

EOLIOS built a digital twin of the site and its surroundings within a 400 m radius, then simulated the most unfavourable conditions: 40 °C outside and a wind of 4 m/s.

View the full study: external CFD study of the PA22 data center in Meudon

The video and the study

The video shows the plumes. The full study presents the temperatures at the equipment intakes, the recirculation identified and the recommendations made.

View the study results: external CFD study of the PA22 data center in Meudon
FAQ

Frequently asked questions

The video, the plumes and the link with the data center study.

What exactly does this video show?

An external CFD simulation of a data center in Meudon: the rooftop hot air plumes, the generator set discharges and their dispersion over the site.

What do the colours mean?

They represent air temperature: red for the hottest air discharged by the equipment, blue for the cooler outside air.

Why simulate 40 °C outside?

It is one of the most unfavourable conditions selected: the equipment must keep cooling even in very hot weather.

What is recirculation?

It is when equipment draws back in the hot air discharged by a neighbouring unit. It makes the dry coolers lose capacity.

Where can I find the study results?

The intake temperatures, the recirculation identified and the recommendations are presented in the full study of the PA22 data center.

Explore the field

Data Center: continue exploring.

CFD expertise, delivered projects and technical dossiers: the whole Data Center field in one place.

CFDExpert engineers
20+Countries
R&DResearch & innovation
Contact

Want to see your project simulated?

The simplest thing is to talk it through together. Our engineers reply with an initial technical read.