External CFD simulation of a data center in Meudon: the hot air plumes from the dry coolers and generator sets, then their path over the wooded site.
Updated on 25 November 2026
In a minute and a half, we see how the discharges from a data center rise, mix and disperse over a site surrounded by woods and buildings.
Click a passage to play it in the player.
This video comes from EOLIOS's external CFD study of the PA22 data center in Meudon. The site's dry coolers and generator sets discharge hot air on the roof.
A temperature isosurface envelops the hot air above the equipment, then streamlines show the generator set discharges. The video ends with the plume carried over the wooded site.
The dry coolers are installed on the roof of the technical rooms that house the generator sets. It had to be confirmed that generator exhaust would not contaminate the air they draw in.
Equipment that releases heat from a water circuit into the outside air using fans. It discharges hot air, and its performance depends on the temperature of the air it draws in.
EOLIOS built a digital twin of the site and its surroundings within a 400 m radius, then simulated the most unfavourable conditions: 40 °C outside and a wind of 4 m/s.
View the full study: external CFD study of the PA22 data center in MeudonThe video shows the plumes. The full study presents the temperatures at the equipment intakes, the recirculation identified and the recommendations made.
View the study results: external CFD study of the PA22 data center in MeudonThe video, the plumes and the link with the data center study.
An external CFD simulation of a data center in Meudon: the rooftop hot air plumes, the generator set discharges and their dispersion over the site.
They represent air temperature: red for the hottest air discharged by the equipment, blue for the cooler outside air.
It is one of the most unfavourable conditions selected: the equipment must keep cooling even in very hot weather.
It is when equipment draws back in the hot air discharged by a neighbouring unit. It makes the dry coolers lose capacity.
The intake temperatures, the recirculation identified and the recommendations are presented in the full study of the PA22 data center.