Thermal and airflow CFD simulation of a data center technical room in Meudon: the existing configuration, then two new designs, shown as streamlines and as temperature and velocity planes.
Updated on 25 November 2026
In just over two minutes, we see how the hot air discharged by the equipment can return to their intakes, and how a suitable design channels it. This is what prevents hot spots in a technical room.
Click a passage to play it in the player.
This video comes from the CFD thermal study of a data center's technical rooms in Meudon, carried out by EOLIOS. Unlike IT rooms, these rooms (UPS, STS, transformers) do not have organised hot and cold aisles.
The video presents the room configuration as streamlines coloured by temperature and as temperature planes at the systems' intake height, then two new designs: a horizontal enclosure and ducts at the system outlets, with the same views for comparison.
In a data center's technical rooms, every installation is different: there are no established measures or ready-made solutions for organising airflow around the equipment.
A phenomenon in which the hot air discharged by the equipment is drawn back in instead of being extracted. It raises the air inlet temperature and encourages hot spots.
EOLIOS built the 3D model of each room from the drawings and site visits, respecting the actual position of the equipment and obstacles, then simulated the existing configuration and several designs.
View the full study: thermal study of a data center's technical roomsThe video compares the designs visually. The full study describes the anomalies found in the existing configuration and the designs adopted for each room.
View the study results: thermal study of a data center's technical roomsThe video, the planes shown and the link with the technical room study.
A CFD simulation of a data center technical room: streamlines coloured by temperature, temperature and velocity planes, for the existing configuration and two new designs.
On the streamlines and temperature planes, red marks hot air and blue cool air. On the velocity planes, they represent air speed.
This is the air the equipment draws in to cool itself. If it is too hot at this height, the equipment risks overheating.
Their equipment is laid out case by case, without hot and cold aisles. Hot air can therefore easily return to the intakes.
The anomalies found and the designs adopted for each room are presented in the full technical room study.
Explore our expertise, projects and technical papers to go further than the FAQ.
CFD expertise, delivered projects and technical dossiers: the whole Data Center field in one place.
The simplest thing is to talk it through together. Our engineers reply with an initial technical read.