CFD simulation of the generator rooms of a data center: velocities and pressures at the generator outlets, then in the discharge duct, for two configurations.
Updated on 25 November 2026
In under a minute, we see where the air discharged by the generators speeds up and where it loses pressure. These pressure losses determine the room's ability to remove heat.
Click a passage to play it in the player.
This video comes from EOLIOS's study of pressure losses in the generator rooms of a data center in Marcoussis. The hot air discharged by the generator sets has to pass through a duct before being released at roof level.
Velocity and pressure sections follow the air at the generator outlets, then in the discharge duct. Two configurations are compared: with a 2.25 m wall and without it.
Generator sets are a data center's last line of defence if the main power supply fails. Their operation depends on the hot air they discharge being removed properly.
The drop in pressure an airflow undergoes when it passes an obstacle: a grille, a bend, a sound attenuator. The greater it is, the harder it is to remove the air.
Sound attenuators, essential against noise, slow the air down. EOLIOS simulated the rooms to characterise these pressure losses and test changes to the ducts.
View the full study: pressure loss study of a generator roomThe video shows the airflows in the configurations compared. The full study presents the improvement achieved and its effect on the discharge at roof level.
View the study results: pressure loss study of a generator roomThe video, the pressure losses and the link with the study of the room.
A CFD simulation of a generator room: velocity and pressure sections at the generator outlets, then in the discharge duct, with and without a wall.
On the velocity sections, red marks fast air and blue slow air. On the pressure sections, they show where the air loses energy.
If the air is slowed down too much, it leaves the roof more slowly and may be drawn back in by nearby equipment.
To measure the effect of one element of the room, here a wall, on the airflow in the discharge duct.
The improvement achieved and its effect on the discharge at roof level are presented in the full pressure loss study.