Hot spots in data centers: causes and effects

EOLIOS takes care of your data center:

Expertise

Continue navigation :

Table of contents

Our latest news :

Our projects :

Our areas of expertise :

Technical files :

What temperature in a data center?

Ashrae standard

The Ashrae (American Society of Heating, Refrigerating and Air-Conditioning Engineers) data center temperature standard is a standardized recommendation for temperature management in data centers.
This standard is regularly updated to take account of technological advances and industry best practices.

Tableau Ashrae - data center - 2023
AHSRAE class according to temperatures maintained in the data center

The Ashrae standard recommends a temperature range for data centers, rather than a specific temperature.
The typical recommended range is between 18°C and 27°C (64°F and 81°F).
This allows flexibility for data center operators, who can adjust the temperature to suit their specific needs.

One of the main aims of this standard is to optimize the energy efficiency of data centers while maintaining appropriate conditions for equipment operation.
Temperatures that are too high can cause components to overheat and systems to fail, while temperatures that are too low can increase cooling system energy consumption .

Hot spots in data centers

Explanation of the main thermo-aerodynamic phenomena

Diagram of aeraulic disturbances in a data center - origins of hot spots

Hot spots in a data center are defined by ASHRAE TC 9.9 as areas where the air entering servers, storage systems, routers or other electronic equipment will be above 27°C.
The rear area of racks and areas in hot aisles are not considered hot spots.
Hot spots can reduce reliability and damage electronic equipment due to the inability to dissipate the heat generated.

Server and hardware manufacturers may justify denial of warranty service for breach of service contract terms by the presence of hot zones.

Play Video
CFD simulation of a data center with generalized overheating (no partitioning)

What kind of parasitic air inlets can there be in a data center?

These are usually unsealed cable entries or cable duct entries from the computer room, air duct slots , slots at the bottom of load-bearing supports, or simply holes in walls or doors.
In the case of the raised floor itself, there may be openings for cable entries, openings under cabinets, redundant perforated plates that may not be located in cold corridors, openings in the floor around the computer room (behind air control units, under power distribution units).

Excessive cooling capacity in a data center can be detrimental to

Surprisingly, a lack of cooling capacity is not the only cause of hot spots. Excessive cooling capacity can lead to hot spots. How can this happen?

If 8 cooling units are needed to cool the data center computer room, and 10 or 12 are installed and running, where, of course, each of the 10 or 12 units will be running with less power (than when only 8 cooling units would have been running).
This leads to a reduction in air supply and load, which in turn leads to the appearance of additional hot zones in areas of low static pressure (dead zones).

Eliminating hot spots in the data center

Protocol for reducing hot spots

The elimination of hot spots in a data center can be achieved in several stages:

1. Temperature monitoring: Use temperature sensors to monitor and identify hot spots in the data center.
This will enable early detection of overheating problems.

2. Efficient server layout: Ensure optimum server layout, maximizing the space between them to allow better air circulation.
Avoid clutter and obstacles that could impede cold air circulation.

3. Use cooling racks: Use cooling racks for servers that generate excessive heat.
These racks can dissipate heat more efficiently and allow better air circulation.

4. Using cable management: Organize cables in an orderly fashion so that they don’t block airflow.
Poorly organized cables can create hot spots.

5. Optimize ventilation and airflow: Ensure good ventilation in the data center.
Ensuring good airflow through the data center will help eliminate hot spots.

CFD simulation of a hot spot in a data center

To ensure proper air circulation in the date center, only the required number of perforated tiles should be installed in the cold corridors of the data center.
Raised floor tiles should not be located in hot aisles or in unused computer room space.
To calculate the number of perforated slabs required in a data center design, please refer to the CFD sizing study.

The location of the diffusion grilles must correspond to the thermal load of each cabinet.
General guidelines for tile placement are given in the table below.

Implementation of hot and cold aisles

The hot and cold aisles of a data center are concepts for managing air circulation to maintain an optimum temperature inside the data center.

The cold aisle is the space where cool air is introduced into the data center.
IT equipment, such as servers, are positioned so as to face this cold aisle, in order to capture and benefit from the fresh air to cool their internal components.

The hot aisle is where hot air is extracted from the data center.
The data center’s air conditioning and cooling systems evacuate the hot air from this aisle, using equipment such as cooling units, fans and heat exhaust ducts.

CFD simulation of a hot spot in a data center

The aim of separating the hot and cold aisles is to maximize cooling efficiency by minimizing mixing between the two types of air.
This reduces the energy consumption needed to maintain the right temperature, and improves the performance and lifespan of IT equipment.

This concept of separating hot and cold air optimizes data center energy costs by minimizing energy losses associated with the mixing of hot and cold air.
It also maintains an even temperature throughout the data center, reducing the risk of equipment overheating.

Why run a CFD simulation of a data center?

CFD simulation provides information on the relationship between the operation of mechanical systems and variations in the thermal load of IT equipment.
With this information, IT and site personnel can optimize airflow efficiency and maximize cooling capacity.

Modélisation de l'élévation en température en entrée de serveur pour un data center
CFD simulation of hot spots in a data center

It is also necessary to seal unused equipment cabinets.
This involves installing blank blanking panels to cover any open space in the rack not occupied by the equipment.
Also seal all lateral gaps between the mounting rails and the cabinet walls, and any openings at the bottom and top of the cabinets.
Do not allow hot air to recirculate from the rear of the cabinet to the front.

Clear as much space as possible under theraised floorfor better air circulation.
Remove unused cables, debris, etc.

To check that everything has been done correctly, measure the temperature at the server entrance, particularly on the top rows of the telecom cabinets.
This can be done using a variety of thermometers: a non-contact IR thermometer; LCD strip thermometers or wireless RF temperature monitors.
If the intake air is too cold or too hot, perforated plates can be added, moved or replaced. This check should be carried out regularly, especially when new equipment is installed or old equipment is dismantled.

Airflow simulation and CFD analysis

To benefit from all these measures, it is necessary tocarefully study the thermal load, the capacity of the cooling equipment and the airflow in the data center’s computer room.

Of course, additional costs will be incurred, but these costs are justified. According to statistics from experts involved inoptimizing data center air-conditioning systems, the minimum reduction in energy consumption thanks to the above actions is between 10% and 36%.

Play Video

Data centers: on the same subject

Thermal study of technical premises

EOLIOS offers thermal optimization solutions specially designed for data center technical rooms.

Find out more

Data Center Fire Simulation

Comprehensive analyses, risk identification and solutions to protect data centers

Find out more

External CFD simulation for data centers

Heat rejection systems share space with generators, and EOLIOS illustrates how to ensure their proper operation.

Find out more

Understanding how a Data Center works

The operation of a data center depends in particular on maintaining the optimum air temperature in the server room.

Find out more